Friday, 07 August 2015 14:02 Written by

SCOT MXP+

SCOPE introduces its next generation of iconic SCOT Series Circuit Breaker Time Interval Meters in all new super light avatars, based on cutting edge microcontroller & embedded technology.

User can choose from two models, SCOT M3K+ and SCOT MXP+ depending on type of testing to be done on circuit breakers.

Features

  • A radically new design makes SCOT the lightest available CB Time Interval Meter.
  • High sampling frequency of up-to 10 KHz offers high timing resolution of 0.1 mS.
  • Mains as well as rechargeable Li-ion battery operated. In built battery monitor and cut off circuit for protection against battery deep discharge.
  • In built real time clock, memory and printer*. Test time stamping on each record enables time references for future use.
  • PC Downloading & Analysis including ‘Trend Analysis’ is possible with “CData SCOT” Software supplied with kit.
  • Instrument debug options like contact status check, command check, memory check, printer check*, PC downloading check are provided.
  • Simple operation. Tests can be conducted even by technicians.
  • Supplied with rugged test lead set, suitable for testing EHV CBs.
  • Enclosed in ultra rugged IP67 class hard molded case.The instrument is supplied with CData software CD, Calibration Certificate, and Test leads suitable for testing of EHV class circuit breakers.
  • Type Tested as per IEC 60068, IEC 61326 & IEC 61010-1. CE marked

Note: * - These features are available only in SCOT MXP+.

Specifications

Parameter SCOT M3K+ SCOT MXP+
Contact Timing Channels 3 (Main contacts of 3 poles connected end to end, simultaneously) 12 ( Up-to 2 Main + 2 PIR contacts per pole, 3 poles simultaneously, i.e. 6 Main + 6 PIR contacts simultaneously)
Sampling Speed 10kC, 5kC, 2kC,1kC & 100C, Selectable
Timing Range 1Sec, 2Sec, 5Sec, 10Sec & 100Sec respectively for above Sampling Speeds
Resolution 0.1 mSec, 0.2 mSec, 0.5 mSec, 1 mSec & 10 mSec respectively for above Sampling Speeds
Accuracy Value ± 0.05% ± 1 digit
Breaker Control Two solid state contacts rated at 35A, 300V AC/DC for breaker operation
Trigger Options Close, Open, Close-Open
Display 4 Line X 20 character backlit LCD
Printer In-built, 58 mm thermal printer (Available only in SCOPT MXP+)
Keypad 5 keys
Memory 1 MB, 100 records, Internal
Inbuilt Battery Li-Ion, 11.1 V, 4 Ah
Battery Charger Input Supply - 100 to 300 VAC, 50/60 Hz ± 10% Output Voltage - 13.5 VDC, 1000 mA
Communication Port USB
Software CData SCOT - For PC Downloading & Analysis, Windows based
Environment 0 to 50°C, Upto 95% RH (Non condensing)
Dimensions 300 x 250 x 200 mm
Instrument Weight 5 kg
  • Breaker Control: Two solid state contacts rated at 35A, 300V AC/DC for breaker operation (Close & Trip).
  • Trigger Options: Open Close, C-O, O-C, O-C-O, and delay between operations configurable.
  • Sampling Speed: 20kC, 10kC, 5kC, 2kC, 1kC selectable.
  • Travel Channels: For linear / rotary resistive transducers. 0-5V DC excitation source in-built.
  • Communication Port : Ethernet port for communication between laptop and instrument
  • Power : 230V AC + 15%, 50Hz + 10%, 70VA Approx
  • Test Leads: Suitable to test Loco VCBs. Leads supplied are of suitable length, thickness, insulation quality & mechanical strength. They have colour coded terminators, quick-fit type rugged clamps & identification labels.
  • Supplied with suitable Test Leads & aluminium transport case
Saturday, 08 August 2015 15:01 Written by

RT Mon

SCOPE introduces, for the first time in the country, the most powerful Real Time On-Line system for continuous monitoring of Circuit Breaker performance in HV / EHV substations.

RTMon consists of Field Unit which is inatalled near CB in IP enclosure, a PC in control room loaded with RTMon software and the communication link between the two.

No. of CBs in one subatation can be monitored by installing one field unit per CB, and they will communicate with central PC.

Features

  • The RTMon system is set up to monitor the signatures/ values of following parameters directly using sensors:
    • Close/ Trip Coil Current, Line/ Fault Current
    • Station DC Voltage
    • Close / Trip Auxiliary Contact Timings (field configurable wet/ dry)
    • Spring charging motor Current & Time
  • RTMon continously monitors static parameters like SF6 gas pressure or density , pneumatic or hydraulic pressure, temperature etc.
  • The RTMon system calculates following parameters:
    • Projected Main Contact Timings.
    • Arcing Time and Fault Clearing Time.
    • Cumulative Fault Current.
  • Provision for mechanism travel available. Can be used if suitable travel transducer with fixture is available.

Features of RTMon Software

  • Viewing, analysis and comparison of test data with previous signatures or pre-set limits.
  • Dynamic calculations on graphical information for easy on-screen analysis
  • I ndication of any abnormality in real time helps planning of diagnostic testing
  • I n a substation having many RTMons, the software stores the signature data in a structured database to relate data to each CB / pole.

Specifications

  • Trigger: Automatic, on coil current or auxiliary contact change over when the circuit breaker operates.
  • Sampling Rate: 10 kHz
  • Auxiliary Contact: 6 Wet OR Dry contacts, field configurable, 15V to 300V DC input of wet contact.
  • Coil Current: Records 'Trip 1' & 'Close' on 3 channels & 'Trip 2' on 3 channels. Total channels 6. Upto 25A.
  • Line/Fault Current: Records Trip/Close Line/Fault currents on 3 channels for 3 phases.
  • Motor Current: Records Motor current upto 25A and spring charging time upto 60 Sec on 3 Channels.
  • Station DC Voltage: Records variation in Station DC voltage during operation on 2 channels upto 250V DC.
  • Spare Channels: 3 Analog input channels (0-5V input) each for SF6 gas and air or hydraulic pressure.
  • Memory: Inbuilt, non volatile, 256 MB flash.
  • Communication: RF, wired or fiber optic communication with remote PC.
Saturday, 05 September 2015 06:06 Written by

SCOT MXP

SCOT Series of CB Time Interval Meters from SCOPE are compact and reliable instruments to measure operation times of all types of HV and EHV circuit breakers under charged switch yard conditions.

SCOT MXP measures, displays and prints CLOSE, OPEN and C-O times in various configurations. The MXP has a special mode to measure PIR closing time.

Features

  • Inbuilt clock to tag date and time of test to the readings.
  • 4 line 20 character back-lit LCD display for menu and results.
  • Inbuilt memory to hold results of last fifty tests.
  • Easy to use menu driven user interface for operation.
  • Diagnostics for instrument condition and calibration watch.
  • Inbuilt printer for printing results.

Specifications

  •  Channels: Maximum eight in PIR mode
  • Control of breaker :Through 300V / 30A SSRs to Trip and Close the connected circuit breaker
  • Output :4 line 20 character backlit LCD,RS 232 C port for downloading data to PC
  • Printer:Inbuilt, thermal printer
  • Paper: Thermal, 55 mm wide roll
  • Test Leads: Set of 15m, wear resistant Test Cables
  • Range : 999 milliseconds maximum
  • Resolution: 1 millisecond
  • Measuring accuracy : Value ± 0.05% ± 1 digit
  • Environment : 0° to 50° C, 95% RH (Non-condensing) Electrical noise normally found in live switchyards of upto 420kV
  • Power: 230V AC ± 15%, 50Hz ± 10%, 25 VA
  • Dimensions: 430 x 345 x 160 mm
  • Weight: 6 kg, instrument
Tuesday, 13 October 2015 05:30 Written by

HISAC Ultima

HISAC Ultima – new generation Circuit Breaker Dynamic Test Set from SCOPE …. The ultimate solution for testing Circuit Breakers of all types. HIASC Ultima is the most complete analyser for checking the dynamic performance of CBs in live EHV switchyards upto 765 kV.

HISAC Ultima can carry out Dynamic Contact Resistance Measurement on SIX breaks of THREE poles in one operation thereby significantly reducing stress on CB & testing downtime.

It offers flexibility to create pre-programmed Test Plans including all test settings for all types of circuit breakers available in a switchyard that can simply be recalled at the time of actual testing. This saves you from doing all settings in switchyards.

The Analysis software offers a range of utilities which enables effective Condition Monitoring of CB by comparing present test data with previous signatures and predicting future performance.

Features

  • Tests all types of circuit breakers - LV, HV & EHV for all critical performance parameters of all the poles / breaks in a single shot.
  • Measures Main/PIR contact timings, bounce, non simultaneity of contacts and auxiliary contact timings.
  • Analyses contact travel characteristics for speed, insertion, contact gap, over-travel and rebound with suitable transducer and mounting fixture.
  • Records trip and close coil current characteristics.
  • Registers the signature of Dynamic Contact Resistance of main and arcing contacts, of all the 6 breaks simultaneously.
  • Displays settings, graphical and tabulated test results.
  • Prints test report in graphical format with test header and calculation footer, on external printer(not supplied).
  • Incorporates powerful and practical Windows™ based Test Manager Software to control & operate instrument; view, analyze and handle graphical test data on a laptop at high resolution.
  • Selects pre-programmed setup parameters and pass/fail limits through software.
  • Connects to CB with wear resistant test leads of sufficient length, having quick-fit connectors, suitable for EHV circuit breakers.
  • Moves easily within switchyard as the set can be mounted on a specially designed Trolley having large wheels & mains supply distribution board.
  • Travel – For evaluating travel characteristics of operating mechanisms, SCOPE offers rotary and linear resistive travel transducers with universal / specially designed fixtures to suit variety of CBs available.
  • DCRM module captures dynamic variation in contact resistance of main & arcing contacts during breaker operation.
  • Each DCRM module has in built independent isolated, rechargeable battery based 100A DC source.
  • The result is plotted in graphical form on the software screen, which can be further analysed for finding parameters such as contact gap, total insertion, arcing tip insertion, main and arcing contact resistance values etc.
  • Additional optional modules are available to measure PIR value and for monitoring Station DC (Coil voltage), Motor current or other static parameters through configurable Analog channels.
  • Type Tested as per IEC 60068, IEC 61326 & IEC 61010-1. CE marked
  • Supplied with suitable Test Leads & aluminium transport cases for instruments.
  • Travel Transducer and fixture as per order based on make, type & rating of CB.

Specifications

Parameter HISAC Ultima
Trigger Options O, C, C-O, O-C, O-C-O
Timing Channel 24 : 4 Main + 4 PIR per pole, 3 poles Simultaneously
Auxiliary Contact Timing Channel 8 : 4 dry + 4 wet Expandable up to 6 Dry + 6 Wet
Best Time Resolution 50μS
Coil Current Channel 3 : Trip / Close coil current
Travel Channel 3 : Travel characteristic
Analog Channel for DCRM Input (Optional) 1 / 2 / 3 / 6 – as per DCRM modules selected
DCRM Resistance Range & Current (Optional) 1000 / 2000 / 4000 / 8000 μΩ Selectable, Current 100A DC
Static Contact Resistance (CRM) Channel As per DCRM modules selected
CRM Resistance Range 1000 / 2000 / 4000 / 8000 μΩ Selectable
Configurable Analog Channel (Optional) Up to 6: For inputs of station battery voltage, PIR value etc.
PIR value Measurement (Optional) 0-5000Ω with the resolution of 1Ω
Sampling Speed 1 / 2 / 5 / 10 / 20 kC Selectable
Display Display of laptop
Operation Interactive menu through laptop
PC Connectivity Ethernet
Printer External through laptop
Memory Memory of laptop
Dimensions Analyser - 500 x 270 x 300 mm, DCRM Rack - 500 x 270 x 250 mm
Instrument Weight Analyser - 12 kg DCRM Rack-18 Kg(3 DCRM modules per Rack)
Power 230 V AC ± 15% , 50Hz ± 10%
Saturday, 05 September 2015 06:37 Written by

SCOT M3K

SCOT Series of CB Time Interval Meters from SCOPE are compact and reliable instruments to measure operation times of all types of HV and EHV circuit breakers under charged switchyard conditions.

Time Interval Meter measures and displays CLOSE, OPEN and C-O times of main contacts of 3 poles connected end to end, simultaneously.

Features

  • Inbuilt clock to tag date and time of test to the readings.
  • 4 line 20 character back-lit LCD display for menu and results.
  • Inbuilt memory to hold results of last fifty tests.
  • Easy to use menu driven user interface for operation.
  • Diagnostics for instrument condition and calibration watch.

Specifications

  • Channels: Three
  • Control of breaker :Through 300V / 30A SSRs to Trip and Close the connected circuit breaker
  • Output :4 line 20 character backlit LCD,RS 232 C port for downloading data to PC
  • Test Leads: Set of 15m, wear resistant Test Cables
  • Range : 999 milliseconds maximum
  • Resolution: 1 millisecond
  • Measuring accuracy : Value ± 0.05% ± 1 digit
  • Environment : 0° to 50° C, 95% RH (Non-condensing) Electrical noise normally found in live switchyards of upto 420kV
  • Power: 230V AC ± 15%, 50Hz ± 10%, 25 VA
  • Dimensions: 430 x 345 x 160 mm
  • Weight: 6 kg, instrument
Friday, 07 August 2015 14:16 Written by

SCOT M3K+

SCOPE introduces its next generation of iconic SCOT Series Circuit Breaker Time Interval Meters in all new super light avatars, based on cutting edge microcontroller & embedded technology.

User can choose from two models, SCOT M3K+ and SCOT MXP+ depending on type of testing to be done on circuit breakers.

Features

  • A radically new design makes SCOT the lightest available CB Time Interval Meter.
  • High sampling frequency of up-to 10 KHz offers high timing resolution of 0.1 mS.
  • Mains as well as rechargeable Li-ion battery operated. In built battery monitor and cut off circuit for protection against battery deep discharge.
  • In built real time clock, memory and printer*. Test time stamping on each record enables time references for future use.
  • PC Downloading & Analysis including ‘Trend Analysis’ is possible with “CData SCOT” Software supplied with kit.
  • Instrument debug options like contact status check, command check, memory check, printer check*, PC downloading check are provided.
  • Simple operation. Tests can be conducted even by technicians.
  • Supplied with rugged test lead set, suitable for testing EHV CBs.
  • Enclosed in ultra rugged IP67 class hard molded case.The instrument is supplied with CData software CD, Calibration Certificate, and Test leads suitable for testing of EHV class circuit breakers.
  • Type Tested as per IEC 60068, IEC 61326 & IEC 61010-1. CE marked

Note: * - These features are available only in SCOT MXP+.

Specifications

Parameter SCOT M3K+ SCOT MXP+
Contact Timing Channels 3 (Main contacts of 3 poles connected end to end, simultaneously) 12 ( Up-to 2 Main + 2 PIR contacts per pole, 3 poles simultaneously, i.e. 6 Main + 6 PIR contacts simultaneously)
Sampling Speed 10kC, 5kC, 2kC,1kC & 100C, Selectable
Timing Range 1Sec, 2Sec, 5Sec, 10Sec & 100Sec respectively for above Sampling Speeds
Resolution 0.1 mSec, 0.2 mSec, 0.5 mSec, 1 mSec & 10 mSec respectively for above Sampling Speeds
Accuracy Value ± 0.05% ± 1 digit
Breaker Control Two solid state contacts rated at 35A, 300V AC/DC for breaker operation
Trigger Options Close, Open, Close-Open
Display 4 Line X 20 character backlit LCD
Printer In-built, 58 mm thermal printer (Available only in SCOPT MXP+)
Keypad 5 keys
Memory 1 MB, 100 records, Internal
Inbuilt Battery Li-Ion, 11.1 V, 4 Ah
Battery Charger Input Supply - 100 to 300 VAC, 50/60 Hz ± 10% Output Voltage - 13.5 VDC, 1000 mA
Communication Port USB
Software CData SCOT - For PC Downloading & Analysis, Windows based
Environment 0 to 50°C, Upto 95% RH (Non condensing)
Dimensions 300 x 250 x 200 mm
Instrument Weight 5 kg
  • Breaker Control: Two solid state contacts rated at 35A, 300V AC/DC for breaker operation (Close & Trip).
  • Trigger Options: Open Close, C-O, O-C, O-C-O, and delay between operations configurable.
  • Sampling Speed: 20kC, 10kC, 5kC, 2kC, 1kC selectable.
  • Travel Channels: For linear / rotary resistive transducers. 0-5V DC excitation source in-built.
  • Communication Port : Ethernet port for communication between laptop and instrument
  • Power : 230V AC + 15%, 50Hz + 10%, 70VA Approx
  • Test Leads: Suitable to test Loco VCBs. Leads supplied are of suitable length, thickness, insulation quality & mechanical strength. They have colour coded terminators, quick-fit type rugged clamps & identification labels.
  • Supplied with suitable Test Leads & aluminium transport case
Friday, 07 August 2015 11:33 Written by

HISAC Swift

SCOPE offers HISAC Swift - Circuit Breaker Operational Analyser for checking the performance of the circuit breakers. The Analyser contains various intelligent measuring modules designed for measuring parameters such as contact timings of Main/PIR & Auxiliary contacts, Close/Trip Coil Current characteristics and Static Contact Resistance of R, Y & B poles simultaneously. The results can be directly viewed on the TFT touch screen display in graphical as well as numerical form. It is possible to print the graph on built-in thermal printer or download record to PC for further analysis on CPLOT software. This all in one instrument is best suited for gang operated CBs.

Features

  • Operations: C, O, C-O, O-C, O-C-O with configurable delays and Static Contact Resistance.
  • Setup: Breaker information data entry and system settings are possible through the touch screen keyboard, which automatically invokes when this menu is selected.
  • Contact Timing: Channels for 3 Main and 3 PIR Contacts with 0.05mS resolution.
  • One internal channel to measure Close and Trip coil current.
  • Three multiplexed channels to measure Contact resistance with 0.1μΩ resolution and range up to 2Ω.
  • TFT color graphical display with touch screen. Displays the menu which is operated through touch screen.
  • Graph is displayed after the operation with full resolution.
  • Printout: Through inbuilt, 56mm thermal printer is provided for printing test header, graph and calculation.
  • Memory: Provided with 2 MB inbuilt memory. Can store up to 75 records.
  • Windows based CPLOT software to download the record to PC through USB connectivity for further analysis & storage.
  • Type Tested as per IEC 60068, IEC 61326 & IEC 61010-1. CE marked

Specifications

Channels Configuration Range Resolution Accuracy
Contact Status  6: 1 main + 1 PIR per pole, 3 poles Simultaneously  Measurement duration 1mS to 4S @ 1kC, 0.05mS to 200mS @ 20kC 1mS @ 1kC 0.05mS @ 20kC Value ±0.05%
± resolution
Auxiliary Contacts 2: Dry / Wet Selectable 15 to 300V DC (for Wet Channels) 1mS @ 1kC 0.05mS @ 20kC Value ± 0.05% ± resolution
Coil Current 1: Trip / Close coil current 1, 2, 5, 10, 25, 50A DC 0.1% of selected range Value ± 1% ± resolution
Contact Res. Channels 3: Multiplexed 3 Channels.10A Max. 200μΩ, 2000μΩ, 20mΩ, 200mΩ & 2Ω, auto ranging 0.1μΩ @200μΩ 1% of range ± resolution
  • Breaker Control: Two solid state contacts rated at 50A, 300V AC/DC for breaker operation.
  • Sampling Speed: 20kC, 10kC, 5kC, 2kC & 1kC selectable.
  • Plot Length:200mS at 20kC, 400mS at 10kC, 800mS at 5kC, 2000mS at 2kC and 4000mS at 1kC
  • Display : 320 x 240 pixel 5.7” color TFT LCD with LED back light, touch screen
  • Printer: 56 mm paper width, thermal printer
  • Environment: 0 to 50 deg C, 95% RH (non condensing).
  • Power: 96-246V AC, 50/60 Hz, 25VA (approx)
Friday, 07 August 2015 13:39 Written by

CBSCOPE

SCOPE introduces CBSCOPE – Loco Circuit Breaker Test System; the ultimate solution for testing Loco Circuit Breakers of all types. CBSCOPE is the most complete analyzer for checking the dynamic performance of Loco VCBs; both Single bottle and Double bottle.

Features

  • CBSCOPE Measures timings, bounce, and simultaneity of contacts
  • Analyses contact travel characteristics for speed, contact gap, overtravel and rebound.
  • Displays settings, graphical and tabulated test results.
  • Incorporates powerful and practical Windows™ based Test Manager Software to control & operate instrument; also to view, analyse and handle graphical test data on a laptop at high resolution.
  • Specially designed test commands for all Loco VCB testing.
  • Analysis of test results provides inputs to assess and correct:
    • Settings for contact timings.
    • Closing and Opening speeds, over-travel, rebound and contact wipe.
    • Trip/Close release mechanism settings.

Specifications

Channels Configuration Range Resolution Accuracy
Contact Timing 3: 2 for double bottle VCB, 1 spare Measurement duration 1 mS to 40 Sec at 1 kC, 0.05 mS to 2 Sec at 20 kC 1 mS at 1 kC 0.05 mS at 20 kC Value ± 0.05% ± resolution
Auxiliary Contacts 2: Trip/ Holding & Close Coil current 1, 2, 5, 10, 25 A DC 0.1% of range at 1A 0.004% of range Value ± 0.5% ± resolution
Voltage (Travel) 2: Travel characteristics 0-5 V DC 1.2 mV at 25A Value ± 0.5% ± resolution
  • Breaker Control: Two solid state contacts rated at 35A, 300V AC/DC for breaker operation (Close & Trip).
  • Trigger Options: Open Close, C-O, O-C, O-C-O, and delay between operations configurable.
  • Sampling Speed: 20kC, 10kC, 5kC, 2kC, 1kC selectable.
  • Travel Channels: For linear / rotary resistive transducers. 0-5V DC excitation source in-built.
  • Communication Port : Ethernet port for communication between laptop and instrument
  • Power : 230V AC + 15%, 50Hz + 10%, 70VA Approx
  • Test Leads: Suitable to test Loco VCBs. Leads supplied are of suitable length, thickness, insulation quality & mechanical strength. They have colour coded terminators, quick-fit type rugged clamps & identification labels.
  • Supplied with suitable Test Leads & aluminium transport case
Tuesday, 11 August 2015 15:33 Written by

SA 30i

SA 30i and SA 10i the Leakage Current Analyser and Leakage Current Meter from SCOPE are two state of the art on-line test system for Residual Life Assessment of metal oxide (Zno) Surge Arresters. The instrument measures and directly displays the values of resistive and total leakage current. it is capable to work accurately and safely in swithchyard upto 765kV.

SA30i measures Third Harmonic Resistive leakage Current (THRC) with system harmonic compensation in accordance with IEC 60099-5 B2 (which is best recommended), whereas SA10i, a hand held Leakage Current Meter measures THRC without system harmonic compensation in accordance with IEC 60099-5 B1.

Features

  • Simple, lightweight, portable, feature-rich, affordable.
  • Measures 3rd harmonic resistive current with system harmonic compensation*, and the total leakage current.
  • In-built temperature measurement facility enables calculation of temperature compensated leakage currents.
  • Results are displayed on LCD, printed on thermal printer and can be stored in the in-built memory of the instrument. 1000 test records can be stored.
  • Built-in standard calibration source for self-calibration check facility.
  • USB communication port to transfer data to PC having Windows based data management software.
  • SA identity creation, Data management, Analysis and Trending through SAData software.
  • Facility for testing of GIS LAs available optionally thorugh Field PT input.
  • The instrument is supplied along with a low noise Clamp-on CT, Field Probe assembly for system harmonics compensation*, Test Leads suitable for EHV class LAs*, Thermal paper roll*, SAData software installation CD and a Calibration Certificate.

* - Features available only in SA30i.

Specifications

Parameter SA 30i SA 10i
 Total Leakage Current Range  Up to 10mA 
 Field Probe Current Range  Up to 10mA 
 Resolution  Up to 1µA  Not available
 Inputs  External Clamp-on CT, Field Probe, External PT (110V AC) - Optional External Clamp-on CT
Display 4 line x 20 character large backlit LCD 2 line x 16 character backlit LCD
Compensation Automatic for Noise, System Voltage, System Harmonic & Temperature Automatic for Noise, System Voltage & Temperature
 Temperature Sensor Inbuilt silicon thermometer Inbuilt silicon thermometer
Self-calibration Check Built-in source available No
PC Connectivity Yes 
Memory 1000 results
Printer Inbuilt Thermal Printer Not available
Battery 11V / 2200mAh, Internal rechargeable Li-ion battery 7.4V / 1150mAh, Internal rechargeable Li-ion battery
Battery charging 100-270V AC, 50 / 60Hz ± 10%, 1 Phase 100-270V AC, 50 / 60Hz ± 10%, 1 Phase
Dimension 415 x 330 x 200mm 190 x 129 x 50mm
Instrument Weight 7.5 kg 1.5 kg
Page 1 of 4