MagD

SCOPE proudly introduces Step-Up Transformer - MagD, specially designed to cater the needs of testing of instrument Transformers. Before new systems are put into service or after any occurrence of fault, the instrument transformers need to be tested for their outputs. It is to be ensured that these instrument transformers are giving proper outputs to the protective relays.

MagD is used to plot excitation curves for instrument transformers. Inbuilt voltmeter and ammeter, eliminates the need of external meters for plotting of curves. It can also be used for de-magnetization of transformer cores and also turns-ratio tests can be conducted using MagD.

Thermal cutoff , Two-hand control and Variac Zero interlock is deployed for user safety and protection.

Features

  • Prepare excitation curves quickly and easily
  • Knee – point test of CTs
  • De-magnetize transformer cores
  • Conduct turns-ratio test of voltage transformers
  • Inbuilt voltmeter and ammeter eliminates the need of external meters
  • HV and LV outputs available separately
  • Online switching between HV and LV outputs
  • Visual Indicators for HV/LV output ON
  • Two-Hand control enhances user safety
  • Interlocking feature for Variac Zero position for user safety
  • Thermal cutoff for instrument and user safety
  • Supplied with specially designed High voltage cables and rugged carrying case

Specifications

Parameters  MagD 20 /21* MagD 30 /31* MagD 50 /51*
HV output

0 to 2200V AC

0.5A (Continuous) / 1A (35s),

10 min Off

0 to 3000V AC

0.4A (Continuous) / 0.8A (35s),

10 min Off

0 to 5000V AC

0.3A (Continuous) / 0.6A (35s),

10 min Off

LV output* 0 to 250V AC, 8A Continuous
Protection Thermal cutoff , Variac zero interlock, Two-hand control
Voltmeter

HV : 0 – 2200V AC

LV* : 0 – 250V AC

HV : 0 – 3000V AC

LV* : 0 – 250V AC

HV : 0 – 5000V AC

LV* : 0 – 250V AC

Ammeter

HV : 0 – 1.5A

LV* : 0 – 10A

HV : 0 – 1A

LV* : 0 – 10A

HV : 0 – 0.5A

LV* : 0 – 10A

Mains Input Supply 230V ± 15%, 50Hz ± 10%, AC
Operating Temperature 0°C to 50°C, Up to 95% RH (Non-Condensing)
Dimension 450 x 500 x 590mm Approx
Weight 46 kg

Accessories

Description Quantity
Aluminium Carrying Case 1 No.
Input Power Supply Cable 2 meter 1 Set
LV Output Cable 5 meter 1 Set
HV Output Cable 5 meter 1 Set