Transformer Testing Equipment

Transformer Testing Equipment (5)

Thursday, 05 May 2016 07:19 Written by

TRM 50+

SCOPE introduces 50 A state of the art precision winding resistance meter, specially designed for field testing as well as factory testing of large transformers up to 500 MVA. Winding resistance value of transformer and rotating machine are directly displayed on 5.7” TFT display. TRM 50 is designed to work in live EHV switchyard conditions, ensuring operator’s safety and repeatability of results. Maintenance time saving is ensured by one time connection to transformer with simultaneous resistance measurement of three / six windings, measurement of resistances of all taps with automated tap change and demagnetization facility. The meter is protected against the back-EMF offered by large inductive windings.

 

Features

  • Can measure DC winding resistance of large rotating machines, highly inductive test objects like Transformer, Generators and Motors etc.
  • 50 A DC current makes it possible to measure low resistances with high accuracy.
  • One time connection to either all windings of primary and / or secondary. Simultaneous measurement reduces connection and measurement time.
  • Change in winding resistance, short or open windings can be detected from measured values.
  • Automatic temperature measurement and temperature corrected value calculation.
  • Measurements of winding resistance of all taps of phases in one go. Recoding, printing and storage of results.
  • OLTC contact opening and compete OLTC performance test facility. Testing of either single or three phases in one test. Single report generation.
  • To know condition of OLTC contacts, OLTC mechanism, transition resistor.
  • Discharges and demagnetizes the object after test.

Specifications

Parameter TRM 50/ TRM 50+
No of Channels  3/6 Current Channels, 3/6 Volatge Channels , 1 tempreture Channel 
Connections One time connection to primary or secondary winding of transformer
Current Ranges 50A, 40A, 25A, 10A, 5A, 1A, 100mA, 10mA
Resistance Ranges Up to 2000 Ω (Auto ranging)
Resolution  4 ½ digit
Accuracy Value ± 0.5% ± 5 counts
Current and Resistance ranges  
Open Circuit Voltage 50 V 
Demagnetization Facility Yes
Display 5.7” TFT display with touch screen
Printer 58 mm, Inbuilt thermal printer
Communication Port Ethernet for PC communication
Data Port USB for extrernal memory stick connection
External Control Possible via Notebook PC through Ethernet port and software
Temperature measurement Range 0 to 100 deg, Accuracy ± 1 deg, Resolution 0.1deg
Temperature correction For Aluminium & Copper 
Temperature Input Channel Compatible to accept RTD input
User Interface Resistive touch screen
Back EMF Protection Yes. Automatic protection after measurement and during accidental disconnection of current path. Protection operates even if Mains supply fails.
Discharge Facility & Indication Automatic Discharge of DUT & messages on screen
Tap Changer Test Detects discontinuity during tap changer test
OLTC Test Facility(Optional) OLTC test facility with current v/s time graph, Single or Three Phases simultaneously. Available in control through PC option only.
OLTC current Ranges 50A, 40A, 25A, 10A, 5A
Protection Shut down of power source on Over voltage, Over current,Over temperature
Indications Polarity reversal, Test connection continuity and discharge
Diagnostics Check At power On instrument does self-check of channels and shows the message
Test Leads Measuring leads, AC supply, earth leads and temperature sensor lead
Operating Environment -10°C to 50°C, 95% RH (non condensing)
Storage Temperature -20°C to 60 °C
Heat Run test Yes
Delta connection Measurement  values of each arm of delta winding is calculated and displayed
One side earthing Instrument is able to do the measurement with one side earthing (with Neutral earthing)
Input Supply 110V AC ±15% 50/60 Hz ±10% Or 220V AC ±15% 50/60 Hz ±10%.
Dimensions 630 x 500 x 302mm
Weight 22 Kg. Approx 
Wednesday, 12 August 2015 12:45 Written by

MagD

SCOPE proudly introduces Step-Up Transformer - MagD, specially designed to cater the needs of testing of instrument Transformers. Before new systems are put into service or after any occurrence of fault, the instrument transformers need to be tested for their outputs. It is to be ensured that these instrument transformers are giving proper outputs to the protective relays.

MagD is used to plot excitation curves for instrument transformers. Inbuilt voltmeter and ammeter, eliminates the need of external meters for plotting of curves. It can also be used for de-magnetization of transformer cores and also turns-ratio tests can be conducted using MagD.

Thermal cutoff , Two-hand control and Variac Zero interlock is deployed for user safety and protection.

Features

  • Prepare excitation curves quickly and easily
  • Knee – point test of CTs
  • De-magnetize transformer cores
  • Conduct turns-ratio test of voltage transformers
  • Inbuilt voltmeter and ammeter eliminates the need of external meters
  • HV and LV outputs available separately
  • Online switching between HV and LV outputs
  • Visual Indicators for HV/LV output ON
  • Two-Hand control enhances user safety
  • Interlocking feature for Variac Zero position for user safety
  • Thermal cutoff for instrument and user safety
  • Supplied with specially designed High voltage cables and rugged carrying case

Specifications

Mains input supply 230V AC ± 5%, 50/60 Hz
Protection Thermal cutoff , Variac zero interlock, Two-hand control
Dimensions Instrument – 500 x 230 x 300 mm
Voltmeter 0 – 250 V AC for LV out
0 – 2.2 kV AC for HV out
Ammeter 0 – 10A AC for LV out
0 – 1A AC for HV out
LV output 0V to 250V AC , 8Amp ; continuous
HV output 0V to 2200V AC, 0.5Amp ; continuous
1Amp for 35 Sec, Rest time – 10 Minutes
Operating temperature 0 to 50 deg C
Humidity 5% to 95% RH, non-condensing
Weight 27 kg

Accessories

Description Quantity
Aluminium Carrying Case 1 No.
Input Power Supply Cable 2 meter 1 Set
LV Output Cable 5 meter 1 Set
HV Output Cable 5 meter 1 Set
Monday, 20 November 2017 06:31 Written by

TTRM 101

SCOPE introduces state of the art precision single phase Transformer Turns Ratio Meter (TTRM ) designed for field testing as well as factory testing of power transformers, instrument transformers and distribution transformers

of all types. TTRM 101 measures only truns ratio where as TTRM 102 along with turns ratio, measures ratio deviation, phase angle deviation, magnetizing current and detects tap-position of single phase transformer in charged switchyard condition. The range of AC voltage selection offers high accuracy in measurement.Both the instrument have in-built TFT display with touch screen and thermal printer. The user friendly, simple instrument makes the testing more easy. With the touch keypad it is possible to enter required DUT information.The ratio results are displayed with % error. Internal non-volatile memory gives the provision of storing test results.Further data can be downloaded to PC or copied to memory stick through USB port provided.

The CTrans-TTRM software, gives the flexibility to download the stored results to PC and do the further analysis and report generation.

Features

  • Different voltage ranges provided for more accurate results
  • 5.7” TFT display with touch screen and simple menus to operate TTRM
  • Facility to configure transformer ID and details
  • Automatic OLTC operation for tap change
  • Date and time stamping to results
  • In-build memory to store the test results
  • Thermal printer to take quick print out for record
  • Ethernet port for PC interface to transfer records to PC Software
  • Mass storage device (USB 2.0) interface for copying records in pen drive
  • Lightweight, portable instrument household in rugged moulded case

 

Specifications

  Parameter Test Voltage      Range     Resolution Accuracy
1
                 
Ratio 10 V 0.8000 – 9.9999 0.0001

0.05 %

10.000 – 99.999 0.001

0.05 %

100.00 – 999.99 0.01 0.05 %
1000.0 – 1500.0 0.1 0.05 %
1500.1 – 2000.0 0.1 0.1 %
2000.1 – 4000.0 0.1 0.2 %
40 V 0.8000 – 9.9999 0.0001 0.05 %
10.000 – 99.999 0.001 0.05 %
100.00 – 999.99 0.01 0.05 %
1000.0 – 4000.0 0.1 0.05 %
4000.1 – 9999.9 0.1 0.25 %
10000 - 13000 1 0.25 %
100 V 0.8000 – 9.9999 0.0001 0.03 %
10.000 – 99.999 0.001 0.03 %
100.00 – 999.99 0.01 0.05 %
1000.0 – 4000.0 0.1 0.05 %
4000.1 – 9999.9 0.1 0.15 %
10000 – 13000 1 0.15 %
13001 - 20000 1 0.20 %
2   

Excitation Current

(Only in TTRM 102)

10 V 2000 mA 0.1 mA ± 1 mA
40 V 500 mA 0.1 mA ± 1 mA
100 V 200 mA 0.1 mA ± 1 mA
 3  Phase Deviation

(Only in TTRM 102)

10V / 40V / 100 V

± 180 Degree 0.01 Degree ± 0.05 Degree

 

Parameters TTRM 101
No of channels single HV channel and single LV channel
Test Voltages 10V, 40V and 100V AC selectable voltages
Measurements Ratio, Ratio error
OLTC Control Raise and Lower control to operate OLTC
Test Results Display (TFT) display, Thermal Printer.
Test Leads Suitable to test EHV Transformers
Printer Inbuilt Thermal Printer
Paper Thermal, 58 mm wide roll form
Memory Inbuilt memory, can store 1000 records, with date and time stamping. USB port to copy record in pen drive
Power (110V ± 15%) / (60Hz ± 10%) OR (230V ± 15%) / (50Hz ± 10%), 75VA..
Communication Port Ethernet port.
Housing Fitted in moulded case
Environment 0: -20°C to 55°C 95%RH (non-condensing) Electrical noise normally found in charged EHV switchyards
Dimensions 435 X 315X 175 mm. (Max.)
Weight 10 Kg Approx
Monday, 25 March 2019 12:28 Written by

TTRM 301

SCOPE introduces state of the art precision three phase Transformer Turns Ratio Meter (TTRM ) designed for field testing as well as factory testing of power transformers, instrument transformers and distribution transformers of all types. Along with turns ratio, this light weight and reliable instrument measures ratio deviation, phase angle deviation, magnetizing current and detects tap-position of single as well as three phase transformers in charged switchyard condition. The instrument has facility to automatically detect vector group of all majority configurations available. The differant AC voltage selection offers high accuracy in measurement.

Instrument has in-built TFT display with touch screen and thermal printer. The user friendly, simple instrument makes the testing more easy. With the touch keypad it is possible to enter required DUT information. The ratio results of all the phases are displayed in tabular form with % error. Internal non volatile memory gives the provision of storing test results. Further data can be downloaded to PC or copied to memory stick through USB port provided. The CTrans-TTRM software, gives the flexibility to download the stored results to PC and do the further analysis and report generation.

Features

  • Different voltage ranges provided for more accurate results
  • 5.7” TFT display with touch screen and simple menus to operate TTRM
  • Facility to configure transformer ID and details
  • Automatic OLTC operation for tap change
  • Date and time stamping to results
  • In-build memory to store the test results
  • Thermal printer to take quick print out for record
  • Ethernet port for PC interface to transfer records to PC Software
  • Mass storage device (USB 2.0) interface for copying records in pen drive
  • Lightweight,portable instrument household in rugged moulded case

 

Specifications

  Parameter Display      Range     Resolution Accuracy
1 Turns Ratio 1.9999 : 1 0.8-20000 : 1 5 Digit

0.8 - 100: ± 0.05% @ 10V

101 - 1000: ± 0.05% @ 10V

1001 - 1500: ± 0.05% @ 10V

1501 - 2000: ± 0.10% @ 10V

2001 - 4000: ± 0.20% @ 10V

 

0.8 - 100: ± 0.05% @ 40V

101 - 1000: ± 0.05% @ 40V

1001 - 1500: ± 0.05% @ 40V

1501 - 2000: ± 0.05% @ 40V

2001 - 4000: ± 0.05% @ 40V

4001 - 13000: ± 0.25% @ 40V

 

0.8 - 100: ± 0.03% @ 100V

101 - 1000: ± 0.05% @ 100V

1001 - 1500: ± 0.05% @ 100V

1501 - 2000: ± 0.05% @ 100V

2001 - 4000: ± 0.05% @ 100V

2001 - 4000: ± 0.05% @ 100V

13001 - 20000: ± 0.20% @ 100V

2 Excitation Current 0.1mA to 1.999A 0-2A 0.1mA ± 1mA
3 Phase Deviation 0.05 Deg to +179.95 Deg ± 180 Deg 0.05 Deg ± 0.05 Deg

 

Parameters TTRM 301
No of channels Three HV channels and three LV channels
Test Voltages 10V, 40V and 100V AC selectable voltages
Measurements Ratio, Ratio error
OLTC Control Raise and Lower control to operate OLTC
Test Results Display (TFT) display, Thermal Printer.
Test Leads Suitable to test EHV Transformers
Paper Thermal, 58 mm wide roll form
Memory Inbuilt memory, can store 1000 records, with date and time stamping. USB port to copy record in pen drive
Power 90V – 265V, 50/60 Hz, 100VA approx.
Communication Port Ethernet port.
Housing Fitted in moulded case
Environment 0 to 50 C, 95% RH (non-condensing) Electrical noise normally found in charged EHV switchyards
Dimensions 435 X 315X 175 mm. (Max.)
Weight 10 Kg Approx

 

Video

Tuesday, 03 May 2016 11:41 Written by

TTRM 302

SCOPE introduces state of the art precision three phase Transformer Turns Ratio Meter (TTRM ) designed for field testing as well as factory testing of power transformers, instrument transformers and distribution transformers of all types. Along with turns ratio, this light weight and reliable instrument measures ratio deviation, phase angle deviation, magnetizing current and detects tap-position of single as well as three phase transformers in charged switchyard condition. The instrument has facility to automatically detect vector group of all majority configurations available. The differant AC voltage selection offers high accuracy in measurement.

Instrument has in-built TFT display with touch screen and thermal printer. The user friendly, simple instrument makes the testing more easy. With the touch keypad it is possible to enter required DUT information. The ratio results of all the phases are displayed in tabular form with % error. Internal non volatile memory gives the provision of storing test results. Further data can be downloaded to PC or copied to memory stick through USB port provided. The CTrans-TTRM software, gives the flexibility to download the stored results to PC and do the further analysis and report generation.

Features

  • Different voltage ranges provided for more accurate results
  • 5.7” TFT display with touch screen and simple menus to operate TTRM
  • Facility to configure transformer ID and details
  • Automatic OLTC operation for tap change
  • Date and time stamping to results
  • In-build memory to store the test results
  • Thermal printer to take quick print out for record
  • Ethernet port for PC interface to transfer records to PC Software
  • Mass storage device (USB 2.0) interface for copying records in pen drive
  • Lightweight,portable instrument household in rugged moulded case

 

Specifications

  Parameter Display      Range     Resolution Accuracy
1 Turns Ratio 1.9999 : 1 0.8-20000 : 1 5 Digit

0.8 - 100: ± 0.05% @ 10V

101 - 1000: ± 0.05% @ 10V

1001 - 1500: ± 0.05% @ 10V

1501 - 2000: ± 0.10% @ 10V

2001 - 4000: ± 0.20% @ 10V

 

0.8 - 100: ± 0.05% @ 40V

101 - 1000: ± 0.05% @ 40V

1001 - 1500: ± 0.05% @ 40V

1501 - 2000: ± 0.05% @ 40V

2001 - 4000: ± 0.05% @ 40V

4001 - 13000: ± 0.25% @ 40V

 

0.8 - 100: ± 0.03% @ 100V

101 - 1000: ± 0.05% @ 100V

1001 - 1500: ± 0.05% @ 100V

1501 - 2000: ± 0.05% @ 100V

2001 - 4000: ± 0.05% @ 100V

2001 - 4000: ± 0.05% @ 100V

13001 - 20000: ± 0.20% @ 100V

2 Excitation Current 0.1mA to 1.999A 0-2A 0.1mA ± 1mA
3 Phase Deviation 0.05 Deg to +179.95 Deg ± 180 Deg 0.05 Deg ± 0.05 Deg

 

Parameters TTRM 302
No of channels Three HV channels and three LV channels
Test Voltages 10V, 40V and 100V AC selectable voltages
Measurements Ratio, Ratio error, Phase angle deviation, Excitation current, vector group
OLTC Control Raise and Lower control to operate OLTC
Test Results Display (TFT) display, Thermal Printer.
Test Leads Suitable to test EHV Transformers
Paper Thermal, 58 mm wide roll form
Memory Inbuilt memory, can store 1000 records, with date and time stamping. USB port to copy record in pen drive
Power 90V – 265V, 50/60 Hz, 100VA approx.
Communication Port Ethernet port.
Housing Fitted in moulded case
Environment 0 to 50 C, 95% RH (non-condensing) Electrical noise normally found in charged EHV switchyards
Dimensions 435 X 315X 175 mm. (Max.)
Weight 10 Kg Approx

 