CFL PL4+
The new generation CFL PL4+ Cable Fault Pre-locator from SCOPE is the ultimate solution for locating underground cable faults in minimum time. It uses advanced technology for fault distance measurement which helps even an unskilled operator to locate the fault accurately up to 256 km.
CFL PL4+ portable Prelocator is used for identification of fault types in underground cables and the distance of fault. These products are designed to find out various types of faults in the cable such as Open Circuit, Short Circuit, Splice in Cable, High Resistance, Moisture Ingress, etc. Various modes of operation combined with advanced features offer the user the most effective solution for the job
Features
- Compact, Lightweight and Rugged
- User-friendly operation
- Wide measurement range up to 256km
- Highest measurement accuracy up to 0.025%
- A high-speed sampling of 800MHz
- Multiple waveform comparison with Subtraction mode to show waveform differences
- Zoom function for detailed analysis of the waveform
- Asynchronous interference & noise suppression
- Adjustable Gain and Balance
- Inbuilt Cable Library for easy setup and testing
- Inbuilt memory to store 300 waveforms with USB connectivity
- High resolution 10.4” colour TFT display
- “Screenshot” function with image saving in JPG
- Mains, as well as Inbuilt Rechargeable Battery, operated
- Housed in IP67 class moulded case
Specifications
Parameters | CFL PL4+ | |||||||
Modes Of Operations |
TDR: Time Domain Reflectometry / Low Voltage Pulse-echo SIM / MIM / ARC : Secondary Impulse / Arc Reflection/Multiple Impulse ICM / ICE: Impulse Current Voltage Decay |
|||||||
Sampling Rate | 800MHz | |||||||
Measurement Range | Up to 256 Km | |||||||
Measurement Accuracy | 0.025% to 0.2% | |||||||
Resolution | 0.01m | |||||||
Pulse Amplitude (OCV) | 18V and 86V selectable | |||||||
Pulse Width | 10nS to 100μS | |||||||
Output Impedance | 25Ω to 600Ω (Default 75Ω) | |||||||
Velocity of Propagation (VoP)/Propagation Factor (PF) Settings | Parameters | VoP% | PF | V/2 | ||||
From | 33.3% | 3.000 | 50m/μS | |||||
To | 99.9% | 1.000 | 150m/μS | |||||
STEP | 0.1% | 0.001 | 0.1m/μS | |||||
Memory | 300 Waveforms | |||||||
Connectivity | USB, Direct Download to Pen Drive | |||||||
Cable Library | >100 Settings | |||||||
Display | 10.4" Colour TFT | |||||||
Battery | Rechargeable Lithium-Ion, Suitable for 6-hour operation | |||||||
Charger Input Supply | 90V to 264V AC, 47 to 63 Hz, Single Phase | |||||||
Environmental | -10°C to +50°C, up to 95% RH (Non-Condensing) | |||||||
Dimension | 339mm x 295mm x 152mm | |||||||
Weight | 3.7 Kg |
CFL PL3+
The new generation CFL PL3+ Cable Fault Pre-locator from SCOPE is the ultimate solution for locating underground cable faults in minimum time. It uses advanced technology for fault distance measurement which helps even an unskilled operator to locate the fault accurately up to 128 km.
CFL PL3+ portable Prelocator is used for identification of fault types in underground cables and the distance of fault. These products are designed to find out various types of faults in the cable such as Open Circuit, Short Circuit, Splice in Cable, High Resistance, Moisture Ingress, etc. Various modes of operation combined with advanced features offer the user the most effective solution for the job.
Features
- Compact, Lightweight and Rugged
- User-friendly operation
- Wide measurement range up to 128km
- Highest measurement accuracy up to 0.01%
- A high-speed sampling of 800MHz
- Multiple waveform comparison with Subtraction mode to show waveform differences
- Zoom function for detailed analysis of the waveform
- Asynchronous interference & noise suppression
- Adjustable Gain and Balance
- Inbuilt Cable Library for easy setup and testing
- Inbuilt memory to store 300 waveforms with USB connectivity
- Equipped with 3 TDR channels for analysing 3 phase cable in single connections
- High resolution 5.7” colour TFT display
- Mains, as well as Inbuilt Rechargeable Battery, operated
- Housed in IP67 class moulded case
Specifications
Parameters | CFL PL3+ | |||||||
Modes Of Operations |
TDR: Time Domain Reflectometry / Low Voltage Pulse-echo SIM / MIM / ARC : Secondary Impulse / Arc Reflection/Multiple Impulse ICM / ICE: Impulse Current Voltage Decay |
|||||||
Sampling Rate | 800MHz | |||||||
Measurement Range | Up to 128Km | |||||||
Measurement Accuracy | 0.01% to 0.2% | |||||||
Resolution | 0.01m | |||||||
Pulse Amplitude (OCV) | 10V and 45V selectable | |||||||
Pulse Width | 10nS to 100μS | |||||||
Output Impedance | 25Ω to 600Ω | |||||||
Velocity of Propagation (VoP)/Propagation Factor (PF) Settings | Parameters | VoP% | PF | V/2 | ||||
From | 33.3% | 3.000 | 50m/μS | |||||
To | 99.9% | 1.000 | 150m/μS | |||||
STEP | 0.1% | 0.001 | 0.1m/μS | |||||
Memory | 300 Waveforms | |||||||
Connectivity | USB, Direct Download to Pen Drive | |||||||
Cable Library | >100 Settings | |||||||
Display | 5.7" Colour TFT | |||||||
Battery | Rechargeable Lithium-Ion, Suitable for 6-hour operation | |||||||
Charger Input Supply | 90V to 264V AC, 47 to 63 Hz, Single Phase | |||||||
Environmental | -10°C to +50°C, up to 95% RH (Non-Condensing) | |||||||
Dimension | 275mm x 255mm x 130mm | |||||||
Weight | 2.5 Kg |
CFL PP3+
The new generation CFL PP3+ Cable Fault Pin Pointer cum route tracer from SCOPE is the ultimate solution for locating of underground cable faults in minimum time by tracing cable route. It uses an advanced technology which helps even an unskilled operator to locate the fault accurately.
For pinpointing it is used along-with CFL SG Series Surge Generators and for route tracing it is used along-with CFL AG Series Audio Frequency Generators. Advanced technology with features like time-lapse measurement, makes it a tool that can tackle complicated faults easily.
Features
- Compact, Lightweight and Rugged
- Operation via User Friendly 5.7” colour Touchscreen Display
- Universal Receiver used for Route Tracing and Pinpointing
- Backlit facility with intensity control for ease of viewing in direct sunlight
- Simultaneous display of Magnetic and Acoustic waveforms
- Time-lapse / delay measurement facility
- Automatic Fault Point Indication using Coincidence Method
- Noise suppression filters to eliminate external influences
- Mute function for headphones to disable noise while moving
- Route guidance (Compass) feature during Pinpointing
- Detection of live loaded cable (50Hz frequency)
- Specially designed lightweight, neck carrying case ensuring minimum strain to the operator
- Inbuilt Rechargeable Battery
- Water-resistant and dustproof design
- Supplied in an IP67 Class Molded Case
Specifications
Parameters | CFL PP3+ |
Channels | Acoustic and Magnetic (Dual Channel) |
Operating Principle | Coincidence Method |
Gain | Up to 120dB adjustable for Acoustic & Magnetic |
Volume limitation warning | 84dB |
Headphone Jack | 3.5mm |
O/P impedance of headphone | 8Ω to 72Ω (32Ω is recommended) |
Acoustic Channel Bandwidth | 70Hz to 3000Hz with automatic filtering |
Magnetic Channel Bandwidth | 120Hz to 20kHz Auto-tuned |
Battery | 11.1V Lithium-Ion Rechargeable |
Charger Input | 90V to 270V AC, 50/60 Hz, Single Phase |
Operating Time | 10 Hours Min (Approx) |
Display | 5.7'', 320 x 240 pixel, Colour, TFT Touch Screen |
Environmental | -20°C to 55°C, 95% RH (Non-Condensing) |
Dimensions of Receiver | 231mm x 90mm x 135mm |
Weight of Receiver | 1.6 kg |
CFL PL2+
The new generation CFL PL2+ Cable Fault Prelocator from SCOPE is the ultimate solution for locating underground cable faults in minimum time. It uses advanced technology for fault distance measurement which helps even an unskilled operator to locate the fault accurately up to 50 km.
CFL PL2+ portable Prelocator is used for identification of fault types in underground cables and the distance of fault. These products are designed to find out various types of faults in the cable such as Open Circuit, Short Circuit, Splice in Cable, High Resistance, Moisture Ingress, etc. Various modes of operation combined with advanced features offer the user the most effective solution for the job
Features
- Compact, Lightweight and Rugged
- User-friendly operation
- Wide measurement range up to 50km
- Highest measurement accuracy up to 0.04%
- A high-speed sampling of 100MHz
- Multiple waveform comparison with Subtraction mode to show waveform differences
- Zoom function for a detailed review of the waveform
- Asynchronous interference & noise suppression
- Adjustable Gain and Balance
- Inbuilt Cable Library for easy setup and testing
- Inbuilt memory to store 100 waveforms
- RS-232 port for communication
- High resolution 5.7” Monochrome LCD display
- Mains, as well as Inbuilt Rechargeable Battery, operated
- Housed in IP67 class moulded case
Specifications
Parameters | CFL PL2+ | |||||||
Modes Of Operations |
TDR: Time Domain Reflectometry / Low Voltage Pulse-echo SIM / MIM / ARC : Secondary Impulse / Arc Reflection/Multiple Impulse |
|||||||
Sampling Rate | 100MHz | |||||||
Measurement Range | Up to 50 Km | |||||||
Measurement Accuracy | 0.04% to 0.4% | |||||||
Resolution | 0.01m | |||||||
Pulse Amplitude (OCV) | 10V | |||||||
Pulse Width | 10nS to 100μS | |||||||
Output Impedance | 25Ω to 600Ω (Default 75Ω) | |||||||
Velocity of Propagation (VoP)/Propagation Factor (PF) Settings | Parameters | PF | V/2 | |||||
From | 1.000 | 50m/μS | ||||||
To | 3.000 | 150m/μS | ||||||
Memory | 100 Waveforms | |||||||
Connectivity | RS-232 | |||||||
Cable Library | >100 Settings | |||||||
Display | 5.7" Monochrome, LCD | |||||||
Battery | Rechargeable Lithium-Ion, Suitable for 8-hour operation | |||||||
Charger Input Supply | 90V to 264V AC, 47 to 63 Hz, Single Phase | |||||||
Environmental | -10°C to +50°C, up to 95% RH (Non-Condensing) | |||||||
Dimension | 270mm x 240mm x 120mm | |||||||
Weight | 2.5 Kg |
Surge Generator
Surge Generator is the backbone of underground cable fault locator test systems. Surge Generator is used with a Prelocator for fault distance measurement and also used with a PinPointer for pinpointing the fault spot.
SCOPE offers CFL SG Series Surge Generators up to 32kV and 2000 Joules. They are compact, rugged, user friendly and have all safety features in place. They are the ideal choice for fault location on all type of power cables. It can also be mounted in a cable test van for quick fault location if one wants to opt for optional van mounted configuration.
For prelocation it is used in ICM (Impulse Current Method) and SIM (Secondary Impulse Method) / MIM /ARC modes. In this modes, one also needs to use SIM Filter for stabilising the arc at fault. For pinpointing it is used as Thumper to create magnetic as well as acoustic signal across the fault, which is sensed by Pin Pointer.
Features
- Compact, Lightweight and housed in a rugged aluminium case
- Available with 16kV and 32kV Models with energy options such as 500J, 1000J, 1500J & 2000J
- Ideal choice for fault location on all type of power cables
- Backbone of Cable Fault Locator System
- Generates short duration high voltage surge for fault break down
- Used to determine the fault distance in conjunction with Prelocator unit
- Repetitive surges applied for pinpointing the exact fault location in conjunction Pinpointing set
- Supports SIM/ARM/MIM method for locating High resistance and flashing faults along with Prelocator and SIM Filter
- Available with optional modes such as DC Hipot, Burn Down and Sheath Fault Locator Mode
Specifications
Parameters | CFL SG1610 / SG 1620 | CFL SG3210/SG3215/SG3220 |
Output Voltage Range | 0- 4, 0-8, 0-16kV | 0-8, 0-16, 0-32kV |
Output Energy | 1000J /2000J | 1000J / 1500J /2000J |
Impulse Period Sequence | Single Impulse / 3S / 6S / 9S or other as desired | |
Measurement Mode Supported | ICM (Impulse Current Method), SIM (Secondary Impulse Method) / MIM / ARC | |
Ouput Indiaction | Moving Coil Meters | |
Power | 230V AC ±10%, 50Hz | |
Housing | Elegant, rugged aluminium housing with trolley mounting | |
Dimension | 484 x 360 x 580 mm | 700 X 700 X 880 mm |
Weight | 65 kg / 70 kg | 95 kg / 105 kg / 115 kg |
Optional 'DC HiPOT' Mode |
||
Voltage | 0-16kV | 0-32kV |
Current | up to 12mA | up to 24mA |
Optional 'Burn Down' Mode |
||
Voltage | 0- 4, 0-8, 0-16kV | 0-8, 0-16, 0-32kV |
Current | 0-90, 0-60, 0-30mA in resp ranges | 0-240, 0-120, 0-60mA in resp ranges |
Optional 'Sheath Fault Locator' Mode |
||
Voltage | 0-8kV | |
Current | 0-60mA | 0-240mA |
Test Timing Interval | Single Impulse / 3S / 6S / 9S or other as desired |
Cable Identification System
After excavation, sometimes it is confusing to identify the right cable from a bunch of cables. Cable Identification is very important for the safety of field personnel – Cutting a wrong cable can be fatal. So, we require a Cable Identification System to identify the wanted cable.
Cable Identification is the most critical and safety-related sequence during all the procedure of Cable Fault Location. The correct identification of a cable out of a bundle of cables, where most of them can be in service, has to be carried out not only carefully, but also by means of an instrument widely eliminating the possibility of human error or misinterpretation.
The Cable Identification System, CFL CIS from SCOPE is the ultimate solution for identifying wanted (dead) cable from a bunch of cables in a trench, pit or cable rack. The SCOPE’s Cable Identification System, CFL CIS is designed to fulfil these most important safety aspects
Features
- Compact, Lightweight and Rugged
- User Friendly LED Indication for Right & Wrong Cable Identification from multiple cables
- Thin and Flexible Current Clamp for easy insertion between closely mounted Cables
- 10 Stage amplifier setting for better signal identification
- Transmitter operation through Mains as well as In-built rechargeable battery
- Transmitter housed in IP67 class moulded case
Specifications
Parameters | CIS |
Pulse Amplitude | Selectable between 100A (55V) / 60A (36V) |
Pulse Sequence | 10 or 20 or 30 pulses/min, User configurable |
Pulse Modulation | Alternative pulse at 1s and 2.5s |
Pulse Width | 72ms |
Display | 4 line x 20 characters backlit LCD |
Power | 90V to 265V AC, 50/60Hz or In-built 11.1V Lithium Ion Rechargeable battery |
Battery Operating time | 6 Hours Min. |
Environmental | -20°C to +55°C, 95% RH (Non-Condensing) |
Dimensions & Weight | 339mm x 295mm x 152mm, 6 Kg approx |
Parameters | CIS-R |
Display Type | LED Scale |
Flexible Clamp | 150mm Diameter |
Sensitivity | 100% at 31Ω loop resistance |
Amplifier | 10 stage gain setting |
Power | 11.1V Lithium-Ion Rechargeable Battery |
Operating Time | 8 Hours Min |
Environmental | -20°C to +55°C, 95% RH (Non-Condensing) |
Dimensions & Weight | 210mm x 124mm x 51mm, 0.7 Kg approx |
CFL SG 3220
Surge Generator is the backbone of underground cable fault locator test systems. Surge Generator is used with a Prelocator and SIM Filter for fault distance measurement and also used with PinPointer Set for pinpointing the exact fault spot.
SCOPE offers CFL SG 3220, Surge Generator with output of 32kV and 2000 Joules. It is ideal choice for fault location on all types of power cables from LV to EHV. CFL SG Series is equipped with different Protections, Interlocks and Auto-discharge Facility to ensure User Safety during operation. User Friendly controls, adequate form factor, contact free HV terminations makes this CFL SG Series most durable and best-designed sets in the segment.
Features
- Compact, Lightweight, and housed in rugged aluminum case
- Ideal choice for fault location on all type of power cables
- Backbone of Cable Fault Locator System
- Generates short duration high voltage surge for fault break down
- Built-in Current Coupler to determine the fault distance in conjunction with Prelocator unit
- Repetitive surges applied for pinpointing the exact fault location in conjunction Pinpointing set
- Supports SIM/ARM/MIM method for locating High resistance and flashing faults along with Prelocator and SIM Filter from CFL Series
- Available with optional modes such as DC Hi-Pot, Burn Down and Sheath Fault Location Mode
- Multiple options in a single instrument to avoid carrying several heavy instruments to the site
- Easy setup and intelligent protections make high voltage testing safe & reliable
- Compatible with other models of SCOPE make CFL Series
Specifications
Parameter | CFL SG 3220 |
Output Voltage Ranges | 0 – 8kV / 16kV / 32kV selectable |
Output Energy | Max. 2000J in each voltage range |
Impulse Sequence (Surge Rate) |
Single Impulse (Manual) / 3 Sec / 6 Sec / 9 Sec or Single Impulse (Manual) / 2 Sec / 4 Sec / 8 Sec (Optional) |
Output Indication | Moving Coil Analog Meter for Output Voltage measurement Moving Coil Analog Meter for Leakage Current measurement in Optional DC Modes |
Measurement Accuracy | ±5% of selected range |
Input Supply | 230V AC ± 10%, 50/60Hz ± 10%, Single Phase, 1.8 kVA max. |
Cooling Type | Air Cooled |
Dimensions | 835 x 810 x 880 mm |
Weight (without trolley and test leads) |
Without Optional DC Modes: 160kg approx. With Optional DC Modes: 165kg approx. |
Environmental (Operation) |
0°C to 50°C, up to 95% RH (Non-Condensing) |
Environmental (Storage) |
-10°C to 55°C, up to 95% RH (Non-Condensing) |
Optional DC Modes | Voltage | Current | Timer / Pulse Ratio* |
Hi-Pot | 0-32kV | 6/12/24mA | 5/10/15min |
Burn Down | 0-8/16/32kV | 240/120/60mA | 3min |
Sheath Fault | 0-8kV | 240mA | *3/6/9s On & 100ms Off |
CFL SG 3210
Surge Generator is the backbone of underground cable fault locator test systems. Surge Generator is used with a Prelocator and SIM Filter for fault distance measurement and also used with PinPointer Set for pinpointing the exact fault spot.
SCOPE offers CFL SG 3210, Surge Generator with output of 32kV and 1000 Joules. It is ideal choice for fault location on all types of power cables from LV to EHV. CFL SG Series is equipped with different Protections, Interlocks and Auto-discharge Facility to ensure User Safety during operation. User Friendly controls, adequate form factor, contact free HV terminations makes this CFL SG Series most durable and best-designed sets in the segment.
Features
- Compact, Lightweight, and housed in rugged aluminum case
- Ideal choice for fault location on all type of power cables
- Backbone of Cable Fault Locator System
- Generates short duration high voltage surge for fault break down
- Built-in Current Coupler to determine the fault distance in conjunction with Prelocator unit
- Repetitive surges applied for pinpointing the exact fault location in conjunction Pinpointing set
- Supports SIM/ARM/MIM method for locating High resistance and flashing faults along with Prelocator and SIM Filter from CFL Series
- Available with optional modes such as DC Hi-Pot, Burn Down and Sheath Fault Location Mode
- Multiple options in a single instrument to avoid carrying several heavy instruments to the site
- Easy setup and intelligent protections make high voltage testing safe & reliable
- Compatible with other models of SCOPE make CFL Series
Specifications
Parameter | CFL SG 3210 |
Output Voltage Ranges | 0 – 8kV / 16kV / 32kV selectable |
Output Energy | Max. 1000J in each voltage range |
Impulse Sequence (Surge Rate) |
Single Impulse (Manual) / 3 Sec / 6 Sec / 9 Sec or Single Impulse (Manual) / 2 Sec / 4 Sec / 8 Sec (Optional) |
Output Indication | Moving Coil Analog Meter for Output Voltage measurement Moving Coil Analog Meter for Leakage Current measurement in Optional DC Modes |
Measurement Accuracy | ±5% of selected range |
Input Supply |
230V AC ± 10%, 50/60Hz ± 10%, Single Phase, 1.8 kVA max. |
Cooling Type | Air Cooled |
Dimensions | 835 x 810 x 880 mm |
Weight (without trolley and test leads) |
Without Optional DC Modes: 150kg approx. With Optional DC Modes: 155kg approx. |
Environmental (Operation) |
0°C to 50°C, up to 95% RH (Non-Condensing) |
Environmental (Storage) |
-10°C to 55°C, up to 95% RH (Non-Condensing) |
Optional DC Modes | Voltage | Current | Timer / Pulse Ratio* |
Hi-Pot | 0-32kV | 6/12/24mA | 5/10/15min |
Burn Down | 0-8/16/32kV | 240/120/60mA | 3min |
Sheath Fault | 0-8kV | 240mA | *3/6/9s On & 100ms Off |
CFL SG 1610
Surge Generator is the backbone of underground cable fault locator test systems. Surge Generator is used with a Prelocator and SIM Filter for fault distance measurement and also used with PinPointer Set for pinpointing the exact fault spot.
SCOPE offers CFL SG 1610, Surge Generator with output of 16kV and 1000 Joules. It is ideal choice for fault location on all types of power cables from LV to EHV. CFL SG Series is equipped with different Protections, Interlocks and Auto-discharge Facility to ensure User Safety during operation. User Friendly controls, adequate form factor, contact free HV terminations makes this CFL SG Series most durable and best-designed sets in the segment
Features
- Compact, Lightweight, and housed in rugged aluminum case
- Ideal choice for fault location on all type of power cables
- Backbone of Cable Fault Locator System
- Generates short duration high voltage surge for fault break down
- Built-in Current Coupler to determine the fault distance in conjunction with Prelocator unit
- Repetitive surges applied for pinpointing the exact fault location in conjunction Pinpointing set
- Supports SIM/ARM/MIM method for locating High resistance and flashing faults along with Prelocator and SIM Filter from CFL Series
- Available with optional modes such as DC Hi-Pot, Burn Down and Sheath Fault Location Mode
- Multiple options in a single instrument to avoid carrying several heavy instruments to the site
- Easy setup and intelligent protections make high voltage testing safe & reliable
- Compatible with other models of SCOPE make CFL Series
Specifications
Parameter | CFL SG 1610 |
Output Voltage Ranges | 0 – 4kV / 8kV / 16kV selectable |
Output Energy | Max. 1000J in each voltage range |
Impulse Sequence (Surge Rate) |
Single Impulse (Manual) - 3 Sec / 6 Sec / 9 Sec or Single Impulse (Manual) - 2 Sec / 4 Sec / 8 Sec (Optional) |
Output Indication | Moving Coil Analog Meter for Output Voltage measurement Moving Coil Analog Meter for Leakage Current measurement in Optional DC Modes |
Measurement Accuracy | ±5% of selected range |
Input Supply |
230V AC ± 10%, 50/60Hz ± 10%, Single Phase, 1.2 kVA max. |
Cooling Type | Air Cooled |
Dimensions |
680 x 480 x 660mm without Optional DC Modes 835 x 810 x 880 mm with Optional DC Modes |
Weight (without trolley and test leads) |
Without Optional DC Modes: 150kg approx. With Optional DC Modes: 155kg approx. |
Environmental (Operation) |
0°C to 50°C, up to 95% RH (Non-Condensing) |
Environmental (Storage) |
-10°C to 55°C, up to 95% RH (Non-Condensing) |
Optional DC Modes | Voltage | Current | Timer / Pulse Ratio* |
Hi-Pot | 0-16kV | 3/6/12mA | 5/10/15min |
Burn Down | 0-4/8/16kV | 90/60/30mA | 3min |
Sheath Fault | 0-8kV | 60mA | *3/6/9s On & 100ms Off |