Transformer Testing >>   Winding Resistance Measurement  








•  

Designed to measure DC winding resistance of highly inductive test objects – Transformers, Generators, Motors etc.

•  

Quick stabilisation of reading even on large test objects by deploying high open circuit voltage

•  

Saves down time, measurement of resistance of 1/2/3 windings simultaneously

•  

Available for continuous testing – powerful, truly continuous DC source with excellent heat management through forced cooling

•  

Total instrument and human safety ensured through automatic & quick back-emf discharge after test completion

•  

Discharge possible through either voltage or current lead in case of accidental lead disconnection – operator risk is minimised

•  

Quick & simple tool to check the condition of OLTC – discontinuity during tap change, if any

•

In-built stable DC source and direct display of resistance value

Single compact instrument

No need to spend time in bridge balancing

No need of manual calculation

• 

Accurate comparison with factory test results at specified temperature possible through Temperature Measurement Channel* & Automatic Temperature correction* facility

• 

Increases testing throughput as complete operation is possible through external PC/Laptop*

• 

Easy to use – self guided operation through interactive menu and keyboard

• 

No need to compensate lead resistance as Kelvin’s Four wire measurement method is used

• 

Designed to work reliably under live EHV switchyard conditions ensuring operator’s safety and repeatability of results

• 

Authentic data management through built-in real time clock*, memory*, PC connectivity* & downloading software*

• 

Tamperproof test results through Inbuilt Thermal Printer*

• 

Housed in rugged aluminium case enhancing transport-worthiness

• 

Supplied with test lead set suitable for EHV class Test Objects having specially designed biting type CK clamps

* Features available only in TRM 25

 Model

TRM 13$ TRM 14$ TRM 103 TRM 104 TRM 104 (5A) TRM 25
 Resistance Channel Two Two Two Two Two Three
 Temperature Channel
 Current Range
 25A
 10A
 5A
 1A
 100mA
 10mA
 Resistance Range
 800
 2m
 4m
 8m
 20m
 40m
 80m
 200m
 400m
 800m

 2

 4
 20
 200
 2000
 Best Resolution 10 1 1 0.1 0.1 0.1
 Accuracy Value ± 0.5% ± 2digits
 Open Circuit Voltage 30V DC 50V DC
 Protection

Back EMF, Over Temperature, Accidental Disconnection of Lead

 Discharge

Automatic

 OLTC Teste

Yes

 Temperature Correction -

Yes

 Display 4 Line 20 character
 backlit LCD

 Resistance & Test Current

256 X 128 pixel,
backlit graphic LCD,
Resistance, Test Current & Temp.

 Memory -

5000 results

 Inbuilt Printer - Yes
 PC Connectivity - Yes
 Power Supply

230V AC ± 15%, 50Hz ± 10%

 Dimension

475 x 405 x 175 mm

475 x 405 x 230 mm

585 x 480 x 195 mm

 Instrument Weight

10kg

10kg

15kg

15kg

15kg

20kg

$ - Models TRM 13 & TRM 14 are designed to test Transformers of rating up-to 1 MVA only.
Winding Resistance Measurement| OLTC Testing | Partial Discharge Measurement
Automatic Trasformer Test System | Bushing Test System
Surge Arrestor Testing | Earth Resistance & Resistivity | Insulation Resistance | Thermo-vision Scanning | Universal Timer |
Industrial Aluminum Cases | Software Solution