Circuit Breaker Testing
Transformer Testing
Instrument Transfomer Testing
Generator & Motor testing
Relay Testing
Bus Bar Testing
Surge Arrestor Testing
Earth Resistance Measurement
Insulation Analysis
Thermovision Scanning
Universal Timers
Software Solutions
Others
 
Surge Arrestor Testing >>   Leakage Current Meter for Surge Arrestor – SA 30i  

State of the art, on-line test system for Residual Life Assessment of Surge / Lightning Arrestors

Immediate assessment of condition of SA through direct display of the 3rd harmonic resistive leakage current and total leakage current in micro-ampere

Accurate and comparable test results made available

Inbuilt system harmonic compensation as per IEC 60099-5 B2

Temperature compensation through inbuilt silicon thermometer

Very fast measurement through specially designed, easily mountable, low-noise clamp-on CT and field probe

Inbuilt rechargeable battery tremendously enhances utility – AC supply connectivity is not required

Built-in self-calibration check facility along with option of revalidating the same with external calibrator

Library of available Surge Arrestors with identification information can be preprogrammed before test and loaded in the instrument for future use

Test results get stored automatically in folder of respective SA and downloaded to PC in similar structure

Authentic, time-stamped test results, data management through built-in real time clock, memory, PC connectivity & downloading software

Tamperproof test results through Inbuilt Thermal Printer

Trend analysis facility in Analysis Software enables present condition assessment and prediction of future performance – enabling a shift form schedule based maintenance to Condition based

Easy to use – self guided operation through interactive menu & keyboard

Designed to work reliably under live EHV switchyard conditions ensuring operator’s safety and repeatability of results

Lightweight, housed in rugged case enhancing transport worthiness

Model

SA 30i
Range
Total Leakage Current Up to 10mA
Resistive Leakage Current Up to 10mA
Field Probe Current Up to 1mA
Resolution 1µA (for all above currents)
Inputs External Clamp-on CT, Field Probe, External PT (110 VAC)
Display 4 line x 20 character backlit LCD
Compensation Automatic for Noise, System Harmonics & Temperature
Temperature Sensor In-built silicon thermometer
Self Calibration Check Yes
PC Connectivity Yes
Memory 1000 results
Printer Inbuilt Thermal Printer
Power supply Internal rechargeable battery
Battery charging 230V AC ± 15%, 50 Hz ± 10%
Dimension 415 x 330 x 200 mm
Instrument Weight 7.5 kg
Surge Arrestor Testing | Earth Resistance & Resistivity | Insulation Analysis| Thermo-vision Scanning | Universal Timer |
Relay Testing | Software Solution
Copyright © SCOPE 2007
Design & Developed by innovativedigits.com