| Circuit Breaker Testing >> |
Dynamic Contact Resistance Measurement |
|
|
|

 |
|
|
DCRM100B:
|
|
Highly portable, easy to connect and use
|
|
Complete instrument- has internal battery for 100A DC, inbuilt charger
|
|
Four wire method of measurement and 100A DC current injection ensures excellent accuracy and repeatability of results
|
|
|
Possible to measure the length of arcing contact when travel trace is
obtained simultaneously on HISAC
|
|
The test report is generated through HISAC analyser and can be directly
printed out or downloaded to IBM compatible PC for evaluation of
dynamic variation of contact resistance
|
|
Evaluation of parameters is possible using SCOPE's CPLOT software
Works reliably under charged switchyard conditions
|
|
| Specifications: |
|
Logic : Bipolar + CMOS
|
|
Housing : Electromagnetically shielded
|
|
Ranges : Full scale 500, 1000 and 2000
|
|
Resolution : 2, 4 and 8, corresponding to respective ranges
|
|
Accuracy : Value ± 2 % ± Resolution
|
|
Curent : 100A DC, for upto 1 second
|
|
Output : 0 to 5 V DC, compatible to HISAC series of Analysers
|
|
Software : CPLOT software for on-screen analysis of test results - optional
|
|
Power : 230V AC ± 15%, 50Hz ± 10%, 20VA approximately
|
|
Test Leads : Calibrated, 15 m long, with special 'Ck' clamps, earthing leads etc
|
|
Weight : 9 kg approx, instrument
|
|
Dimensions : 430 x 315 x 170 mm
|
|
Environment : 0 to 50°C, 95% RH non-condensing; switchyard environment
|